Join to our online upcoming free webinars...

Voltage monitoring relay in 3P with fixed levels HRN-55N

3 x 172-287 V
with NEUTRAL

EAN: 8595188137232 | Code: 7513

DESCRIPTION

  • Relay monitors phase sequence and failure, exceeding of monitored voltage in 3-phase main.
  • HRN-55: supply from all phases, which means that function of relay is applicable also if 1-phase fails.
  • HRN-55N: supply L1, L2, L3-N, it means that relay also monitors break of neutral point.
  • Fixed delay T1 (500 ms) and adjustable delay T2 (0.1 - 10 s).

TECHNICAL PARAMETERS

  • Phase failure: Yes
  • Phase sequence: Yes
  • Overvoltage: x (fixed)
  • Undervoltage: x (fixed) 
  • Asymmetry: x
  • Monitored range: AC 3 x 172-287 V
  • AC 3 x 172-287 V: 1x CO, 8 A
  • Housing: 1-MODULE
  • Power supply: from monitored voltage
  • Dimensions: 90 x 17.6 x 64 mm (3.5˝ x 0.7˝ x 2.5˝)